Is it the case that per ASHRAE/IES 90.1 the maximum possible wattage for the fixture will be applied?The fixture wattage to be used in the power calculation depends on the type of lighting technology (see ASHRAE/IES Standard 90.1-2001, Section 9.2.5, or visit the section of this website that explains Standard 90.1-2001). Consult lighting designers and manufacturers as to what wattage would be appropriate for "lamp/auxiliary" combinations for fixtures with permanent or remote ballasts or transformers. There was a question about the maximum lamp/ballast wattage for light fixtures that use energy-saving (25W, 28W and 30W) T8 lamps. If the ballast can operate these as well 32W lamps, would a 32W lamp have to be assumed for the energy calculations? The industry requested guidance from ASHRAE, which responded:
This indicates that the actual wattage of fluorescent systems using energy-saving T8 lamps can be used in energy calculations, not the maximum lamp-ballast wattage, for the purposes of achieving efficiency levels for the purposes of qualifying for the Commercial Buildings Deduction.
|