Appendix i: Table 9.3.1.1 Lighting Power Densities Using Building Area Method from ASHRAE/IES Standard 90.1-2001
| Building Area Method |
Lighting Power Densities (W/sq.ft.) |
| 1989 |
1999 |
2001 |
2004 |
| Automotive Facility |
0.96 |
1.5 |
1.5 |
0.9 |
| Convention Center |
2.07 |
1.4 |
1.4 |
1.2 |
| Court House |
1.44 |
1.4 |
1.4 |
1.2 |
| Dining: Bar Lounge/Leisure |
1.37 |
1.5 |
1.5 |
1.3 |
| Dining: Cafeteria/Fast Food |
1.37 |
1.8 |
1.8 |
1.4 |
| Dining: Family |
1.37 |
1.9 |
1.9 |
1.6 |
| Dormitory |
1.15 |
1.5 |
1.5 |
1.0 |
| Exercise Center |
2.07 |
1.4 |
1.4 |
1.0 |
| Gymnasium |
2.07 |
1.7 |
1.7 |
1.1 |
| Healthcare Clinic |
1.44 |
1.6 |
1.6 |
1.0 |
| Hospital |
1.44 |
1.6 |
1.6 |
1.2 |
| Hotel |
1.15 |
1.7 |
1.7 |
1.0 |
| Library |
1.29 |
1.5 |
1.5 |
1.3 |
| Manufacturing Facility |
0.96 |
2.2 |
2.2 |
1.3 |
| Motel |
1.15 |
2.0 |
2.0 |
1.0 |
| Motion Picture Theater |
2.07 |
1.6 |
1.6 |
1.2 |
| Multi-Family |
1.15 |
1.0 |
1.0 |
0.7 |
| Museum |
2.07 |
1.6 |
1.6 |
1.1 |
| Office |
1.26 |
1.3 |
1.3 |
1.0 |
| Parking Garage |
1.03 |
0.3 |
0.3 |
0.3 |
| Penitentiary |
1.44 |
1.2 |
1.2 |
1.0 |
| Performing Arts Theatre |
2.07 |
1.5 |
1.5 |
1.6 |
| Police/Fire Station |
1.44 |
1.3 |
1.3 |
1.0 |
| Post Office |
1.44 |
1.6 |
1.6 |
1.1 |
| Religious Building |
2.07 |
2.2 |
2.2 |
1.3 |
| Retail |
2.25 |
1.9 |
1.9 |
1.5 |
| School/University |
1.29 |
1.5 |
1.5 |
1.2 |
| Sports Arena |
2.07 |
1.5 |
1.5 |
1.1 |
| Town Hall |
1.44 |
1.4 |
1.4 |
1.1 |
| Transportation |
2.07 |
1.2 |
1.2 |
1.0 |
| Warehouse |
1.03 |
1.2 |
1.2 |
0.8 |
| Workshop |
0.96 |
1.7 |
1.7 |
1.4 |
|